EPA UCMR 5 PFAS Monitoring Data

PFAS in Wisconsin Drinking Water

Detection data from EPA UCMR 5 monitoring (20232025)

Last updated: May 28, 2026

Monitoring results are not compliance determinations. Detection levels reflect a specific sample point and date. Utilities may have taken corrective action after sampling. Methodology

Under the EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5), public water systems are required to test for 29 PFAS compounds between 2023 and 2025. This page summarizes the monitoring results reported for 189 water utilities in Wisconsin, drawn directly from EPA's published occurrence data. 22 utilities reported one or more samples above an EPA Maximum Contaminant Level for PFOA, PFOS, PFNA, PFHxS, or HFPO-DA.

Highest PFOA / PFOS detections reported

UtilityAnalyteValue (ng/L)
Saukville Waterworks
WI2460134
PFOS
31.00Above MCL
Tomahawk Waterworks
WI7350127
PFOA
21.00Above MCL
Kewaskum Waterworks
WI2670112
PFOA
15.00Above MCL
Marshfield Utilities
WI7720165
PFOS
14.00Above MCL
Weston Municipal Utilities
WI7370163
PFOS
13.00Above MCL
Pewaukee City Water and Sewer Utility
WI2680214
PFOS
12.00Above MCL
Prairie Du Chien Waterworks
WI6120250
PFOS
11.00Above MCL
Prescott Waterworks
WI6480243
PFOA
9.90Above MCL
Rib Mountain Water Utility
WI7370660
PFOS
9.40Above MCL
Pewaukee City Water and Sewer Utility
WI2680214
PFOA
8.50Above MCL

Source: EPA UCMR 5 occurrence data. Detection levels reflect a single sample at a specific point in the system on the date shown. The EPA's Maximum Contaminant Level for PFOA and PFOS is 4 ng/L (finalized April 2024, compliance required by 2029). EPA UCMR 5

PFAS analytes — detection breakdown

PFHxSMCL 10 ppt
87 / 1,227
PFBS
84 / 1,225
PFBA
60 / 1,225
PFPeA
57 / 1,223
PFHxA
44 / 1,223
PFOAMCL 4 ppt
39 / 1,225
PFOSMCL 4 ppt
31 / 1,225
PFHpA
13 / 1,223

Detections / total records per analyte. All 29 UCMR 5 analytes shown where records exist for Wisconsin.

All WI utilities with PFAS records

189 systems
Water System
Milwaukee Waterworks
Milwaukee
View
Madison Water Utility
Madison
View
Green Bay Waterworks
Green Bay
View
Racine Waterworks
Racine
View
Kenosha Water Utility
Kenosha
View
Appleton Waterworks
Menasha
View
Waukesha Water Utility
Waukesha
View
Eau Claire Waterworks
Eau Claire
Above MCL
View
Janesville Water Utility
Janesville
View
West Allis Waterworks
West Allis
View

How this data was collected

Source dataset

All records on this page are drawn from the EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) occurrence dataset, published by the U.S. Environmental Protection Agency. UCMR 5 required large public water systems (serving more than 3,300 people) to sample for 29 PFAS compounds between 2023 and 2025. EPA UCMR 5 occurrence data

Sampling methodology

Samples were collected at entry points to the distribution system (EPTDS) as required by UCMR 5 regulations. Each utility collected at least four quarterly samples during the monitoring period. Results represent concentrations at the specified sample point on the sample date — not a continuous measure of system-wide levels.

Unit normalization

Source data may express concentrations in micrograms per liter (µg/L, also written ug/L or ppb) or nanograms per liter (ng/L, also called ppt). All values on this page are normalized to ng/L (ppt) for consistent comparison with EPA Maximum Contaminant Levels (MCLs). Conversion: 1 µg/L = 1,000 ng/L. Records with unrecognized units are excluded from numeric aggregates and flagged in the raw export.

What "detection" means

A result is counted as a detection when the EPA reports it as "Detected above MRL" — meaning the analyte was measured at or above the minimum reporting limit (MRL) for that analyte. Non-detect results (below MRL) are included in total record counts but not in detection counts. Detection is a monitoring outcome, not a compliance determination.

Validation and exclusion criteria

Records are included only where validated = true and suppressed = false. Records flagged during ingestion for format errors, duplicate source hashes, or missing required fields are excluded.

Update cadence

Pages are regenerated every 24 hours via Next.js ISR. The underlying dataset is updated when EPA publishes new UCMR 5 occurrence data. The source retrieval date shown on each record reflects the date the EPA file was last downloaded to our system.

Cite this page

Water Utility Report. (2026). PFAS in Wisconsin drinking water: EPA UCMR 5 monitoring records (2025). Retrieved May 28, 2026, from https://waterutilityreport.com/data/pfas/wisconsin

Detection levels represent results from EPA-required compliance monitoring at the time of sampling. They are not a real-time indicator of current water quality. Utilities may have taken corrective action or installed treatment after sampling. For current information about your water, contact your utility or consult your annual Consumer Confidence Report.

At a Glance

Utilities tested

189

Total PFAS records

35,479

With detections

of 189

50

Above PFOA MCL (4 ng/L)

of 189

15

Above PFOS MCL (4 ng/L)

of 189

12

Above any individual MCL

PFOA, PFOS, PFNA, PFHxS, or HFPO-DA

22
Earliest sampleJanuary 3, 2023
Latest sampleOctober 22, 2025

Raw data

Download all 35,479 records for Wisconsin as CSV.

Download CSV (35,479 records)