EPA UCMR 5 PFAS Monitoring Data

PFAS in Tennessee Drinking Water

Detection data from EPA UCMR 5 monitoring (2023–2025)

Last updated: November 24, 2026

Monitoring results are not compliance determinations. Detection levels reflect a specific sample point and date. Utilities may have taken corrective action after sampling. Methodology

Under the EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5), public water systems are required to test for 29 PFAS compounds between 2023 and 2025. This page summarizes the monitoring results reported for 86 water utilities in Tennessee, drawn directly from EPA's published occurrence data. 37 utilities reported one or more samples above an EPA Maximum Contaminant Level for PFOA, PFOS, PFNA, PFHxS, or HFPO-DA.

Highest PFOA / PFOS detections reported

UtilityAnalyteValue (ng/L)
Savannah Valley U.d.
TN0000613
PFOA
35.00Above MCL
Fort Campbell Water System
TN0000820
PFOS
27.30Above MCL
Trenton Water System
TN0000707
PFOS
27.00Above MCL
First U.d. of Hardin County
TN0000546
PFOS
25.90Above MCL
Camden Water Dept
TN0000090
PFOS
24.00Above MCL
North U.dep. of Decatur/benton Co
TN0000883
PFOS
20.30Above MCL
Jackson Water System
TN0000299
PFOS
20.00Above MCL
Savannah Valley U.d.
TN0000613
PFOS
18.00Above MCL
First U.d. of Hardin County
TN0000546
PFOA
17.30Above MCL
Clifton Water Dept
TN0000119
PFOS
17.00Above MCL

Source: EPA UCMR 5 occurrence data. Detection levels reflect a single sample at a specific point in the system on the date shown. The EPA's Maximum Contaminant Level for PFOA and PFOS is 4 ng/L (finalized April 2024, compliance required by 2029). EPA UCMR 5

PFAS analytes — detection breakdown

PFBS
149 / 149
PFBA
94 / 94
PFHxA
77 / 77
PFPeA
69 / 69
PFOSMCL 4 ppt
68 / 68
PFOAMCL 4 ppt
63 / 63
PFHxSMCL 10 ppt
21 / 21
PFHpA
21 / 21

Detections / total records per analyte. All 29 UCMR 5 analytes shown where records exist for Tennessee.

All TN utilities with PFAS records

86 systems
Water System
Knoxville Utilities Board - Kub
Knoxville
View
Consolidated U.d. of Rutherford Co
Murfreesboro
View
Tennessee American Water
Chattanooga
View
First U.d. of Knox County
Knoxville
View
Murfreesboro Water Department
Murfreesboro
Above MCL
View
Kingsport Water Dept
Kingsport
Above MCL
View
Cleveland Utilities
Cleveland
View
Jackson Water System
Jackson
Above MCL
View
Columbia Power and Water Systems
View
Franklin Water Dept
Franklin,Franklin Pike
View

How this data was collected

Source dataset

All records on this page are drawn from the EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) occurrence dataset, published by the U.S. Environmental Protection Agency. UCMR 5 required large public water systems (serving more than 3,300 people) to sample for 29 PFAS compounds between 2023 and 2025. EPA UCMR 5 occurrence data

Sampling methodology

Samples were collected at entry points to the distribution system (EPTDS) as required by UCMR 5 regulations. Each utility collected at least four quarterly samples during the monitoring period. Results represent concentrations at the specified sample point on the sample date — not a continuous measure of system-wide levels.

Unit normalization

Source data may express concentrations in micrograms per liter (µg/L, also written ug/L or ppb) or nanograms per liter (ng/L, also called ppt). All values on this page are normalized to ng/L (ppt) for consistent comparison with EPA Maximum Contaminant Levels (MCLs). Conversion: 1 µg/L = 1,000 ng/L. Records with unrecognized units are excluded from numeric aggregates and flagged in the raw export.

What "detection" means

A result is counted as a detection when the EPA reports it as "Detected above MRL" — meaning the analyte was measured at or above the minimum reporting limit (MRL) for that analyte. Non-detect results (below MRL) are included in total record counts but not in detection counts. Detection is a monitoring outcome, not a compliance determination.

Validation and exclusion criteria

Records are included only where validated = true and suppressed = false. Records flagged during ingestion for format errors, duplicate source hashes, or missing required fields are excluded.

Update cadence

Pages are regenerated every 24 hours via Next.js ISR. The underlying dataset is updated when EPA publishes new UCMR 5 occurrence data. The source retrieval date shown on each record reflects the date the EPA file was last downloaded to our system.

Cite this page

Water Utility Report. (2026). PFAS in Tennessee drinking water: EPA UCMR 5 monitoring records (2025). Retrieved November 24, 2026, from https://waterutilityreport.com/data/pfas/tennessee

Detection levels represent results from EPA-required compliance monitoring at the time of sampling. They are not a real-time indicator of current water quality. Utilities may have taken corrective action or installed treatment after sampling. For current information about your water, contact your utility or consult your annual Consumer Confidence Report.

At a Glance

Utilities tested

86

Total PFAS records

566

With detections

of 86

86

Above PFOA MCL (4 ng/L)

of 86

24

Above PFOS MCL (4 ng/L)

of 86

31

Above any individual MCL

PFOA, PFOS, PFNA, PFHxS, or HFPO-DA

37
Earliest sampleJanuary 23, 2023
Latest sampleNovember 18, 2025

Raw data

Download all 566 records for Tennessee as CSV.

Download CSV (566 records)